MODEL |
|
EP 500 |
EP 1000 |
EP 1500 |
EP 2000 |
|
CAPACITY |
VA/W |
500VA/300W |
1000VA/600W |
1500VA/900W |
2000VA/1200W |
|
INPUT |
Nominal
Voltage |
110/120VAC
or 220/230/240VAC | |||
|
|
90-145VAC
or 170-280VAC (Narrow Range) | ||||
|
Voltage
Range |
50-145VAC
or 90-280VAC (Wide Range) | ||||
|
OUTPUT |
Voltage |
120VAC
or 230VAC | |||
|
|
Voltage
Regulation(Batt. Mode) |
-0.555555556 | |||
|
|
Frequency |
50Hz
or 60Hz | |||
|
|
Frequency
Regulation (Batt. Mode) |
+/-0.1
Hz | |||
|
|
Output
Waveform |
Modified
Sine-wave | |||
|
BATTERY
& CHARGER |
Charger
Current |
8
Amp +/- 1Amp |
10
Amp +/- 1Amp |
10
Amp +/- 1Amp |
10
Amp +/- 1Amp |
|
DC
Voltage |
12V
+/- 0.2V |
12V
+/- 0.2V |
24V
+/- 0.4V |
24V
+/- 0.4V | |
|
|
14.5V
+/- 0.3V charger stops and |
| |||
|
Overcharge
Protection |
fault |
29V
+/- 0.6V charger stops and fault | |||
|
TRANSFER
TIME |
Typical |
8ms
Typical | |||
|
EFFICIENCY |
AC
to AC |
>95% | |||
|
DC
to AC |
>80% | ||||
|
INDICATOR |
AC
Mode |
Green
lighting | |||
|
Battery
Mode |
Yellow
lighting | ||||
|
Battery
Charging Mode |
Green
flashing every 2 seconds | ||||
|
Overload |
Red
flashing every 0.5 second | ||||
|
Fault |
Red
lighting | ||||
|
AUDIBLE
ALARM |
Low
Battery at Battery Mode |
Sounding
every 2 seconds | |||
|
Overload |
Sounding
every 0.5 second | ||||
|
Fault |
Continously
sounding | ||||
|
PROTECTION |
Full
Protection |
Discharge,
overcharge, and overload protection | |||
|
PHYSICAL |
Dimension
(DxWxH) mm |
224
X 255 X 80 | |||
|
Net
Weight (kgs) |
2 |
2.3 |
2.5 | ||
|
ENVIRONMENT |
Operating
Environment |
0-
40°C, 0-90 % relative humidity
(non-condensing) | |||
|
Noise
Level |
Less