MODEL |
SS
210 |
SS
220 |
SS
230 |
INPUT |
| ||
Power
(kVA) |
1 |
2 |
3 |
Voltage |
160
- 280 VAC | ||
Frequency |
50
/ 60 Hz. ± 5 % | ||
Power
Factor |
>0.98 | ||
OUTPUT |
| ||
Output
Power Factor |
0.7 | ||
Voltage |
220VAC
/ 230VAC | ||
Voltage
Regulation |
±%2 | ||
Frequency |
50
/ 60 Hz (Auto Detection) | ||
Frequency
Regulation |
±0,5% | ||
Harmonic
Distortion |
<
3 % (For Linaer
Loads) | ||
Crest
Factor |
3:01 | ||
Overload
Capacity |
100%
- 120% for 60 seconds, 120% - 150% for 10
seconds | ||
Whole
efficiency |
>85% | ||
Inverter
efficiency |
>90% | ||
Transfer
Time |
0ms | ||
Outlets |
3pcs
IEC & 1pc Schuko
Outlets |
3pcs
IEC & 2pcs Schuko
Outlets |
6pcs
IEC & 2pcs Schuko
Outlets |
BATTERY |
| ||
Type |
Maintenance-free
lead acid batteries | ||
Recharge
Time |
8
hours (to 90% of full capacity) | ||
Voltage |
36VDC |
72VDC |
96VDC |
Quantity |
3
pcs 12V 7ah |
6
pcs 12V 7ah |
8
pcs 12V 7ah |
Back
Up Time Full
Load |
8
min |
7
min | |
Half
Load |
20
min |
15
min | |
DISPLAY |
| ||
LED
Display |
line
input, inverter, bypass, fault, overload, battery low, self-test,
Load/Battery Level | ||
ALARMS |
| ||
|
Line
Failure, Battery Low, Transfer To Bypass, Failure
Events | ||
PROTECTION |
| ||
|
short
circuit, over temperature, overload, high voltage, battery
low | ||
COMMUNICATION |
| ||
Interface |
RS-232 | ||
(Communication
Port) | |||
Monitoring
and Management Software |
standard | ||
ENVIRONMENT |
| ||
Temparature |
0°C
- 40°C | ||
Humidity |
0%-95% | ||
Noise
Level (1m Distance) |
<45dBA | ||
Protection
Class |
IP20 | ||
PHYSICAL
SPECIFICATIONS |
| ||
Tower
Type |
| ||
Net
Weight(kg) |
15 |
29 |
35 |
Dimensions
(mm) WxHxD |
147x401x223 |
130x475x360 |
190x450x360 |
19"
Rack Mount Type |
| ||
Net
Weight(kg) |
16 |
28 |
37 |
Dimensions
(mm) WxHxD |
483x390x88 |
483x485x130 |
483x460x192 |
STANDARDS |
| ||
Standards |
EN
62040-1-1 (safety), EN 62040-2
(EMC) |