MODEL |
SES 210 |
SES 220 |
SES 230 |
INPUT |
| ||
Power (kVA) |
1 |
2 |
3 |
Voltage Range |
110VAC - 300VAC ( @ 0% to 25% Load ) | ||
140VAC - 300VAC ( @ 25% to 50% Load ) | |||
160VAC - 300VAC ( @ 50% to 100% Load ) | |||
Frequency |
45Hz - 65Hz | ||
Power Factor |
=>0.99 ( @full linear load ) | ||
OUTPUT |
| ||
Output Power Factor |
0.7 | ||
Voltage |
220VAC / 230VAC / 240VAC | ||
Voltage Regulation |
<±1% ( till low battery warning signal ) | ||
Frequency ( Synchronized range ) |
3Hz or 1Hz ( selectable ) | ||
Frequency ( Battery Mode ) |
50 / 60Hz±0.1% | ||
Harmonic Distortion |
<3% ( @full linear load ), <6% ( @full non-linear load ) | ||
Crest Factor |
3:01 | ||
Output Waveform |
Sinusoidal | ||
Overload Capacity |
100% to 105% : Continous / 106%-120% : 30 seconds / 121%-150% : 10 seconds / >150% : transfer to bypass | ||
Line Mode efficiency |
±>86% |
±>87% |
±>88% |
Battery Mode efficiency |
±>85% |
±>86% |
±>87% |
Transfer Time ( AC to DC ) |
0ms | ||
Outlets |
3pcs IEC and 1pc Schuko |
3pcs IEC and 2pcs Schuko |
6pcs IEC and 2pcs Schuko |
BATTERY |
| ||
Type |
Maintenance-free lead acid batteries | ||
Recharge time ( up to 80 % ) |
5hours | ||
Voltage |
24VDC |
48VDC |
72VDC |
Quantity |
2 pcs 12V 7ah |
4 pcs 12V 7ah |
6 pcs 12V 9ah |
Back Up Time Full Load |
3 min | ||
Half Load |
10 min |
| |
Cold Start |
YES | ||
DISPLAY |
| ||
LED Display |
Normal Mode, Battery Mode, Bypass Mode, Self-Test, Weak-Bad Batery, Site Wiring Fault, Fault, Overlaod, Load/Battery Level | ||
ALARMS |
| ||
Battery |
Buzzer Sound once every 1.5 secods | ||
Low Battery |
Buzzer Sound once every 0.2 secods | ||
Overload |
Buzzer Sound once every 3 secods | ||
Normal alarm |
Buzzer Sound once every 3 secods | ||
Fault |
Countinous Buzzer Sound | ||
PROTECTION |
| ||
Short Circuit |
Bypass Mode: Fuse, Normal Mode: Output Breaker / Electronic Circuit, Battery Mode: Output Breaker / Electronic Circuit | ||
Battery |
Battery Discharge Management | ||
EPO |
UPS shuts down immidiately | ||
Over Temperature |
Normal Mode: Transfers to Bypass Mode, Battery Mode: UPS shuts down immidiately | ||
COMMUNICATION |
| ||
Interface |
RS-232 | ||
(Communication Port) | |||
Monitoring and Management Software |
standard | ||
Options |
Dry Contact Board, USB Board, SNMP Card | ||
ENVIRONMENT |
| ||
Temparature |
0°C - 40°C | ||
Humidity |
0% - 90% ( without condensation ) | ||
Noise Level(1m Distance) |
<50dBA | ||
Protection Class |
IP20 | ||
PHYSICAL SPECIFICATIONS |
| ||
Tower Type |
| ||
Net Weight(kg) |
12 |
22 |
27 |
Dimensions (mm) WxDxH |
144x360x220 |
152x438x322 |
190x438x322 |
STANDARDS |
| ||
Standards |
EN 62040-1-1 (safety), EN 62040-2(EMC) |