ODEL

SDM3110

SDM3115

SDM3120

Power(kVA)

10

15

20

INPUT

 

Phase Number

3Phase

Nominal Voltage

380/400V

Minimum Voltage

140

Minimum Voltage ( at full load )

260

Maximum Voltage

480

Frequency

45-65 Hz

Power Factor

>0,97 %

OUTPUT

 

Nominal Voltage

220V / 230V (adjustable)

Wave Form

Pure Sine Wave

Total Harmonic Distortion at

<3%

100% linear load

Frequency

50Hz or 60Hz (adjustable)

Frequency Tolerance(line synchronized)

0,005 %

Static Voltage Regulation (0%-100% load)

<1%

Crest Factor

3

Overload (on mains)(0-150% overload)

>30 sec

>30 sec

>30 sec

Overload (on battery)(0-150% overload)

>30 sec

>30 sec

>30 sec

Total Efficiency

> 91%

Greenmode efficiency

> 97%

BATTERY

 

Type

Maintenance Free Dry Type

Number of Batteries ( standard/internal)

20pcs 12V 9Ah

24pcs 12V 12Ah

28pcs 12V 12Ah

Back up time ( at nominal load )

6min

5min

5min

Recharging Time

< 4 h / 8 h

Discharge Current Wave

< 10%

BY-PASS

 

Voltage Tolerance

10% (adjustable)

Frequency Tolerance

3Hz (adjustable)

Transfer Time

0 ms

PROTECTION

 

Overload Protection

bypass transfer time is calculated by simulating a temperature related model of a fuse

Short Circuit Protection

acts as the ideal current source during the short circuit time

Other Protection

against excessive (heat,voltage,current) intense battery discharge

COMMUNICATION INTERFACE

 

RS 232

Isolated according to EN60950

Free Contact

Isolated according to EN60950

ENVIRONMENT

 

Operating Temperature

0 °C.... + 40 °C

Storage Temperature

-15 °C.....+55 °C

Proposed Temp. to extend battery life

20 - 25 °C

Humidity

< 95%

Audible Noise at 1 m

<55 dB

PHYSICAL SPECIFICATIONS

 

Net Weight( with internal batteries )

81

170

185

Dimensions(cm) (WxDxH)

25,5x60,3x70

43x71x88

STANDARDS

 

Safety

EN50091-1

EMC

EN50091-2

Performance

EN62040-3, EN 50091-3

Protection Class

IP 20