INPUT |
|
Voltage |
136
to 280VAC (normal operation at nominal load) |
90
to 135VAC (derating operation at 0,66 of the
nominal load) | |
Frequency |
45-65Hz |
Inrush
Current |
<10A |
Power
Factor |
0.99 |
Input
THD |
<3% |
Efficiency |
>91% |
Input
Current |
<14A
(at 136V, Nominal load) |
OUTPUT |
|
Voltage |
48VDC
(Nominal) |
45-63VDC
(Clearing Value) | |
53.5VDC
(Factory pre-set) | |
Output
Current |
30Amp |
Current
Share |
±5% |
Short
Circuit Current |
34Amp |
Output
Regulation |
<200mV
(0-100% static load variation) |
<1V
(5-100% load variation) | |
<100mV
(±20% AC variation) | |
<200mV
(0°C-40°C temperature variation) | |
AC
Ripple |
<50mV
AC (at 100Hz) |
ENVIRONMENT |
|
Operating
Temperature |
0°C-40°C |
Relative
Humidity |
5%-95% |
Acustic
Noise |
<50dBA |
PHYSICAL
SPECIFICATIONS |
|
Cooling |
Forced
and Conventional |
Dimensions
(mm) WxDxH |
132x305x342 |
Net
Weight |
11.5 |