MODEL

PDS 500

PDS 600

PDS 800

PDS 1000

Output Power (kVA)

500

600

800

1000

Output Power (kW)

400

480

640

800

INPUT

 

Voltage

380V / 400V / 415V 3 Phase+Neutral+PE

Tolerance

± 15%

Frequency

50 - 60 Hz

Tolerance

± 10%

DC Ripple Voltage

± 1%

DC Ripple Current

max 2% of battery capacity defined in Amps

OUTPUT

 

Power Factor

0.8

Voltage

380V / 400V / 415V 3 Phase+Neutral+PE

Tolerance

 

static condition

±1%

step load (0%-100%-0%)

±8% recovering within tolerance into 2 cycles

step load (0%-50%-0%)

±3% recovering within tolerance into 2 cycles

Total Harmonic Distortion

< 2% (@ 100% linear load)

Crest Factor

3:1 with 80% load

Frequency

50 or 60 Hz.

Frequency tolerance (free running)

± 0.01%

Frequency tolerance (synchronized with utility)

±5%

Overload

 

125% load

10 min

150% load

1 min

Overall Efficiency

0.925

Output Neutral Rating

2

BATTERY

 

Type

Maintenance-free lead acid batteries

Quantity

32 pcs 12V Blocks

Nominal DC Voltage

384VDC

Float Voltage at 20C

436VDC

Automatic and Manual Battery Test

Standard

STATIC BYPASS

 

Input Configuration

Common with Rectifier or Seperate

Transfer Limits

± 10% of Nominal Adjusted Output Voltage

Overload Capability

Continous at 110%

Short Circuit Capability

5min @ 200% and half cycle @ 1000% (non repetitive)

ENVIRONMENT

 

Audible Noise

<68dBA

<70dBA

Operating Temperature

0-40°C

Relative Humidity (non condensing)

0-95%

Protection Class

IP 20

PHYSICAL SPECIFICATIONS

 

Weight Without Battery (kg)

2900

3100

3800

4000

Dimensions (mm) WxDxH

3400*1000*1800

3400*1400*1800

4200*1400*1800

STANDARDS

 

 

EN 62040-1-1 (safety), EN 62040-2(EMC), EN 62040-3 (VFI-SS-111)