GENERAL

 

Input Voltage

380V/400V/415V

Phase Configuration

3Ph+N+PE or 1Ph+N+PE

Rectifiers

Modular and hot swappable RD2000 rectifiers (30Ampere each)

Output

The output distribution fuses can be configured depending on the customer request

Display Options

System Position, Alarms can be monitored and adjustments can be done through LCD display on the Control Unit (CU).

Controller (CU)

All the adjustments and the calibrations are done through CU.

Alarm Contact Outputs

There are total 3 dry contact signals present on the frame for remote monitoring

PROTECTIONS

 

Input

One fuse for each rectifier module.

Output

For DC distribution, up to 350A, total 24pcs fuses can be Installed on the frame

Battery

Fuse according to the frame type for each battery bank

Battery low voltage Disconnect

Battery low voltage contactor for the protection of batteries from deep discharge

High Voltage

High Voltage Protection Module protects the unit from lightning and sudden voltage fluctuations

ELECTRICAL PERFORMANCE

 

Efficiency

>91%

Power factor

99%

Regulation

<1V

BATTERY MANAGEMENT

 

Battery

On 180A frame, there are two group battery banks. Additionally external batteries can be connected to the frame. 8 x 19" 155Ah batteries can be Installed to standard PS8000 frame.

Charge

Auto Charge Mode; 49V Mode, 53.5V Mode, 57V Mode, 63 V Mode especially for wet batteries If any adjustment is not made on the CU menu, then the system shall start to operate at auto charge mode when it is Switched on.

Low Voltage Disconnect

Low voltage disconnect contactor, disconnects the circuit at the adjusted value between 42VDC to 46VDC from the CU(Control Unit)  as s/w or h/w. Low Voltage Disconnect Contactor protects the batteries from deep discharge.

Heat Compensation

Heat Compensation is applied according to the heating profiles of batteries connected either Internally or externally.

ENVIRONMENTAL SPECIFICATIOMS

 

Dimensions (DxHxW) (mm)

395x490x525

Weight(kq/cabinet)

121kg -frame- (excluding the rectifiers and batteries)

Operating altitude (m)

<2500

Relative Humidity

5%-95%

Audible Noise

<50dB

Cooling

Natural and Forced