PARAMETERS TECHNICAL | |||||||
TYPE |
MIPS03 |
MIPS05 |
MIPS06 |
MIPS08 |
MIPS010 | ||
Power(kVA) |
3.15 |
5 |
6.3 |
8 |
10 | ||
The
nominal power of the transformer should be
maximum |
10
kVA | ||||||
It
should be Single Phase. In case of it being 3 Phase then the L-L Voltage
should be 250 |
Voltage
should be 250 | ||||||
PARAMETERS
ELECTRIC | |||||||
INPUT | |||||||
phase
Configuration |
2
in 1 phase + N + PE | ||||||
nominal
Voltage |
230V
AC | ||||||
nominal
frequency |
50/60
Hz | ||||||
frequency |
45-65
(?10%) | ||||||
OUTPUT | |||||||
nominal
Voltage |
230V
AC | ||||||
nominal
frequency |
50/60
Hz | ||||||
overload |
>
60 s at 150% load | ||||||
Efficiency
in normal operation, the nominal load, linear |
>98
% | ||||||
power
factor |
0.8 | ||||||
PARAMETERS TRANSFORMER | |||||||
The
Initial Current value must be |
less
then 8In | ||||||
phase
Configuration |
2
in 1 phase + N + PE | ||||||
Temperature
measurement of transformer windings |
continuous | ||||||
No
Load Condition Current must comply the |
Io
< % 3 condition. | ||||||
The
Short Circuit Voltage must comply the |
Uk
< % 3 condition | ||||||
Rate
of heat loss in the case of no-load Of nominal
capacity |
<
% 3 | ||||||
The
leakage current of the transformer secondary side |
<150
?A | ||||||
PARAMETERS STATIC
SWITCH | |||||||
phase
Configuration |
1Ph+N+PE | ||||||
voltage
control |
The
two input lines and one output line (for
switching) | ||||||
The
scope of the phase voltage changes |
220/230/240V
AC + -10% | ||||||
thyristor
control |
so | ||||||
Jobs
Auto / Manual |
so | ||||||
The
range of changes in frequency bypass |
47
Hz - 63 Hz | ||||||
nominal
current |
50/100
A | ||||||
Transfer
time [ms] |
5ms | ||||||
ENVIRONMENT | |||||||
Operating
Temperature |
-25
° C ... + 40° C | ||||||
Humidity |
up
to 90% (non-condensing) | ||||||
|
| ||||||
STANDARDS | |||||||
Standards |
IEC60364-7-710:2002-11,
section | ||||||
|
VDE
0107,IEC 61558-2-15, IEC 742 | ||||||
Standard
protection class |
IP
20 | ||||||
maximum
temperature |
According
to the category B of the transformer insulation system allows a maximum
temperature 75°C | ||||||
COMMUNICATION | |||||||
relay
contacts | |||||||
port
magistrali CAN | |||||||
Converting
to TCP (optional) | |||||||