CPS7500

 

Capacity (VA / Watts)

7500VA / 5250W

Input

Voltage Range

140Vac – 300Vac

Frequency Range

45Hz - 65Hz (Auto Sensing)

DC Input Voltage

48V

Battery Pack Expansion

Yes

Output

Number of Phase

Single Phase

UPS Outlets (Numbers)

(2) UK type + (1) terminal block or (2) Schuko + (1) terminal block or (2) FR + (1) terminal block

On Battery Output Voltage

Pure SineWave at 220Vac +/- 10%

On Battery Output Frequency

50 / 60 Hz +/- 1%

Over Voltage Protection

Surge to 400V

Transfer Time

< 10 ms

Overload Protection*

On Utility: Circuit Breaker

On Battery: Internal Current Limiting

AVR

Boost& Buck

Charging Current

45Amps

Manual Switch mode

Bypass Only

Surge Protection and Filtering

Lightning / Surge Protection

Yes

Physical

Dimensions(H x W x D)(mm)

440 x 370 x 355

Weight (kg)

55

Wheels

Yes

Status Indicators

Indicators

Power On

Audible Alarms

On Battery, Low Battery, Overload

Multi-function LCD Readout

Yes

Communication

PowerPanel® Software

-

Management

Connectivity Ports

-

SNMP/HTTP Capable

-